• non contact level measurement
  • robust design, without mechanical components
  • easy calibration by means of TEACH-IN method
  • output signal: 4-20 mA or 0...10 V
  • electrical connection: cable or plug M12
  • max. pressure: atmosperic, max. temperature: 70 °C
  • 5 measuring ranges:
    60...500 mm to 600...6000 mm

More informations

Ultrasonic level sensors measure the clearance between a liquid level and the sensor's transmission surface using the echo time measurement of an ultrasonic signal.

Liquid levels can be measured and the data sent to master evaluators by means of a programmable current or voltage output.

For operating ranges up to 2 m, the devices are available in an M18 enclosure incl. two lock nuts that is easy to install. For an operating range up to 3,5 m, we offer an M30 enclosure. The sensor with 6 m operating range has a housing with square flange and an extra large transmission surface.

Typical applications

FUM10 ultrasonic level sensors are suitable for applications where liquid levels in depressurized vessels are monitored, measured or regulated.

PDF Information

For Further Information

E-mail to This email address is being protected from spambots. You need JavaScript enabled to view it.

Electronic Level Measurement

Copyright MAXXmarketing GmbH